GENERAL ISSUES

The transformer poles are indicated by adding the letter (T) in front of the pole symbol

Transformer pole selection: The selection is made according to the tables used for the selection of the Medium Voltage (MV) and Low Voltage (LV) poles as well as the principles for the selection of the power distribution poles

The transformer platform is sized to carry all types of transformers, up to 250 and 400 kVa (included) and indicated with the symbol (PLT-250 or 400)

Platform for the transformer poles: the platform is installed according to the transformer power, line voltage and sectional dimensions, but not less than 250 cm from the top